Honeywell CC-PAIH02 16-Channel HART High Level Analog Input Module
Manufacturer: Honeywell Process Solutions
Model: CC-PAIH02 (P/N:51405038-375)
Series: Experion PKS C300 Series C I/O System
Type: 16-channel configurable single-ended/differential HART high level analog input IOM
Function: Collect 4–20mA, 1–5V, 0–5V analog signals from HART smart transmitters; transparent HART5/6/7 bidirectional communication, full channel fault diagnosis, built-in loop power supply for two-wire field instruments
1. Overview
CC-PAIH02 is a mainstream HART analog input module for Honeywell Experion PKS C300 DCS, improved version of CC-PAIH01. It supports mixed wiring configuration: 12 single-ended + 4 differential channels, compatible with 4–20mA two-wire smart transmitters and voltage signal sensors. Built-in transparent HART modem supports HART 5/6/7 protocols, realizing remote calibration, secondary variable reading, device predictive health diagnosis and parameter configuration. Matched IOTA terminal bases: non-redundant CC-TAIX01, redundant CC-TAIX11. Equipped with 1500V channel-to-backplane galvanic isolation, RC anti-interference filter, hot-swap online maintenance and G3 conformal coating. Widely deployed in power, petrochemical, oil & gas and water treatment sites with large quantities of HART smart pressure/temperature/flow transmitters.
2. Technical Specifications
• Power Supply: 24 VDC ±10%, typical power consumption 4.4W / 185mA
• Channel Configuration: 16 total channels (12 single-ended / 4 differential software configurable)
• Supported Signal Types: 4–20mA (250Ω built-in sampling resistor), 1–5VDC, 0–5VDC
• HART Protocol: Transparent pass-through for HART 5, HART 6, HART 7; point-to-point & multi-drop compatible
• ADC Resolution: 16-bit Δ-Σ high precision analog-to-digital conversion
• Static Accuracy: ±0.075% FS @25°C; ±0.15% FS full operating temperature range
• CMRR: 70dB DC~60Hz, suppress industrial power frequency common-mode noise
• Filter Characteristic: Single-pole RC filter, -3dB cutoff at 6.5Hz
• Galvanic Isolation: 1500V RMS channel-to-backplane isolation per channel
• Built-in Diagnostics: Wire break, short circuit, over-range, reverse polarity, HART communication loss LED alarm
• Fixed Scan Cycle: 50ms full 16-channel sampling period
• Operating Temperature: -40°C ~ +70°C (G3 coated extended version); 0°C ~ +60°C standard
• Storage Temperature: -40°C ~ +85°C
• Humidity: 5%~95% RH non-condensing environment
• Dimensions: 142 mm × 82 mm × 54 mm
• Weight: Approx. 0.37 kg
• Conformal Coating: G3 coating for corrosive, damp, dusty cabinet environments
• Maintenance Feature: Hot-swappable, replace module without disconnecting field instrument cables
• Compatible IOTA Bases: CC-TAIX01 (non-redundant simplex), CC-TAIX11 (redundant)
• Certifications: CE, UL, CSA, Class 1 Div 2 hazardous area certified
3. Key Features
• 16 Mixed Single-Ended/Differential HART Channels Flexible wiring selection for long-distance field cables to eliminate ground loop interference
• Full HART 5/6/7 Compatibility Real-time access to secondary variables, remote calibration, device health predictive diagnostics without extra hardware
• 16-bit High Precision Conversion & Low Temperature Drift Stable measurement accuracy for long-term continuous process operation
• High CMRR Anti-Interference Circuit Effectively filter 50/60Hz power frequency noise in factory electrical environments
• Comprehensive Per-Channel Self-Diagnosis Visible LED fault indication for rapid on-site troubleshooting
• Hot-Swap Online Maintenance Design Module replacement without stopping control loops or powering down cabinet
• G3 Conformal Coating Protection Resist dust, moisture and corrosive industrial gas in harsh control cabinets
• Dual Redundancy Architecture Support Matches simplex and redundant IOTA bases for high-availability DCS control systems
4. Applications
• Thermal & Combined Cycle Power Plant mass HART pressure/temperature/flow transmitter centralized signal acquisition
• Refinery & Petrochemical full-process smart instrument analog signal monitoring and HART device management
• Oil & Gas long-distance pipeline and compressor station multi-point process variable measurement
• Large water treatment, metallurgy and pharmaceutical continuous process smart transmitter monitoring loops
Honeywell © CC-PAIH02 16-Channel HART High Level Analog Input Module